Jump to navigationJump to search| Primary | |
|---|---|
| Nominal primary supply temperature | 85°C |
| Maximum primary supply temperature | 90°C * |
| Minimum primary supply temperature | 55°C ** |
| Maximum primary differential pressure | 250kPa |
| Minimum primary differential pressure | 50kPa *** |
| Pressure class DH circuit | PN16 |
| Domestic Hot Water | |
| Nominal DHW supply temperature | 55°C |
| DHW Set Range | 45°C to 60°C |
| Domestic Hot water heat exchanger (DHW) | E8LAS‐40 |
| Keep Warm Modes | Economy / Comfort |
| Keep Warm Temperature | 25°C to 60°C |
| Keep Warm Duration | 0 to 120 mins or Always On |
| Max Return Temperature during Keep Warm Mode | DHW Setpoint -2°C |
| DHW Max pressure | 6 Bar |
| Pressure class DHW circuit | PN10 |
| DWH Priority | Multi-Stage **** |
| Central Heating | |
| Maximum flow temperature | Primary T -5°C |
| Return Temp Limit Range | 35°C to 55°C |
| CH Limit Range | 30°C to 80°C |
| Central heating heat exchanger (CH) | B25TH‐30 |
| Pressure class CH circuit (3 bar safety valve) | PN16 |
| CH working pressure | N/A (By Installer) |
| Nominal pump pressure | 20 kPa (Adj. 0-70) |
| Maximum recommend flow rate | 750 l/hr |
| General | |
| Primary connections | DN32 Female |
| Mains & DHW connections | ¾” Female |
| Central heating connections | ¾” Female |
| Casing width | 653mm |
| Casing height | 900mm |
| Casing depth | 225mm |
| Casing Material | Steel |
| HIU Insulation Material | EPP Expanded Polypropylene |
| Pipework Insulation Material | Grey Polyethylene Foam |
| Maximum Heat Losses | <50W (1.2 kWh/day) |
| Weight (basic version) | 35kg Approx |
| Electrical supply info | 230V 50Hz - 0.64A |
| Power consumption per year | circa 45kWh |
| Fuse ratings | 3 Amp |
| Sensors | NTC 10kohm @ 25°C |
.* Maximum primary supply temperature 100°C for momentary spikes.
.** Minimum required DH supply temperature is DHW setpoint + 5°C with a minimum of 55°C.
.*** Depends on requested DHW output and available DH supply temperature.
.**** See Multi-Stage DHW Priority example below.