Technical Data

{{#section:The_DATA_and_DATA_PLUS_HIU|Technical Data}}

Description Data
Nominal primary supply temperature 80C
Maximum primary supply temperature 85C
Nominal DHW supply temperature 55C
DHW Set Range 45C to 60C
Return Temp Limit Range 45C to 70C ?
CH Limit Range 45C to 80C
Primary connections ¾” Female / 18mm
Mains & DHW connections ¾” Female / 18mm
Central heating connections ¾” Female / 18mm
Pressure relief 15mm
Domestic Hot water heat exchanger (DHW) E8AS‐24 or E8AS‐36
Central heating heat exchanger (CH) E8T‐36
Maximal primary differential pressure (without dP regulator) 250kPa
Maximal primary differential pressure (with dP regulator) 400kPa
Minimal primary differential pressure 50kPa
Pressure class DH circuit PN16
Pressure class CH circuit (3 bar safety valve) PN10
Pressure class DHW circuit PN10
Casing width 490mm
Casing height 640mm
Casing depth 275mm
Casing Material EPP Expanded Polypropylene
Maximum Heat Losses 50W (1.2 kWh/day)
Typical Heat Losses (DHW Only, Keep Warm) 25W ?
Weight (basic version) 24kg
Electrical supply info 230V 50Hz
Fuse ratings 3 Amp
Sensor DHW NTC 10kohm @ 25deg
Keep Warm Modes Economy / Comfort
Max Return Temperature during Keep Warm Mode DHW Setpoint - 2C