Diversity
Danish DS439
https://docs.google.com/spreadsheets/d/1TtprDWpiO6NmWu6S8g5v00gYaIJC5v9B30qqNb8nUSw/edit?usp=sharing
Coincidence Factor for DS439
This represents the peak load on a network as a percentage of the sum total of individual peak loads (Number x 37.6kW).
Studies
Scaling Diversity for Larger Properties
A larger property may have an HIU sized for higher peak flow rate, so how does this affect diversity?
With the Danish diversity at 37.6kW for a standard property, if we use am 75.4kW HIU, it is a common mistake is to base diversity on doubling the calculation.
So for example, Danish for 10 properties is 89kW. It would be wrong to say if these properties had 80kW HIUs that the peak load will be 178kW.
178kW would, by Danish standard, deliver enough power for around 37 properties.
A better approach, would be to treat one of the larger properties as 2 standard properties.
Then the peak diversified load for the 10 properties (= 20 standard) would be 126kW.
In summary, to scale diversity, one does not scale on power, but rather scale the number of properties using the number of standard 37.6kW properties that would deliver the same total power before diversity.
For example:
50 single bathroom properties with a peak of 45kW, plus 25 double bathroom properties with a peak of 75kW Equivalent number of properties = (50 * (45/37.6)) + (25 * (75/37.6)) = 110 standard properties Peak diversified DHW load (Danish) = 346kW
Live Anonymous Diversity
https://heatweb.fred.sensetecnic.com/api/public/graph/dhwload
This data provides 3 variables as standard, in one second resolution:
- DHW flow rate (litres/minute)
- DHW Power delivered (kW) based on mains at 10C and recorded output temperature
- How many systems running
The following graph uses the same data but overlaps days to simulate more properties, although overestimates diversity loading.
https://heatweb.fred.sensetecnic.com/api/public/graph/public_overlay.csv
Ways to Reduce Peak Load
- Shift heating load.
- Keep heating constant,
- Heating on earlier on the coldest days (optimum start), to avoid morning surge.
- Hot water cylinder.
- Set peak rate costs, from 7:30 to 8:30 on cold Winter weekdays.
- Peak rate on/off indicated to user so they can choose to avoid a peak rate time. No charge for draw-offs that start in cheap rate but continue into peak.
- Option to have heating linked to auto-off during peak times.
- Option to reduce DHW temperature at peak. Doesn't reduce load, but increases primary dT (reduces flow).
Minimum Load
It becomes clear from data that a more common condition than peak load, is no load, with short moments of demand lasting but a few seconds.
Substations or central plant designed to meet peak loads may struggle with the low trickle flows in standby or the speed of response from a single tap opening. There may well be enough buffering in pipework to overcome fluctuations, and the correct use of central buffer storage and jockey (low load) pumps covers the problem, but systems fed by boilers instantaneously may cause boiler cycling and inefficient operation.
A particular problem may exist on systems where the network is expected to expand. The plantroom will be built to cover the final load, possibly a whole estate, but the initial connection to smaller numbers will push the limits of low load.
Low Load Storage
Storage may be used to cover low load issues, as well as high loads.
A 250 litre buffer store would cover the overnight loads of many properties, removing the need for low load demand on the plantroom. When the plantroom fires it will be to recharge low load buffers in a single burn, then go back to sleep.
Buffer stores would have their own pump (and non-return valve), typically 180kPa peak, for supplying minimum network DP at no/low load, and a valve in parallel with the pump to control recharge. See Distributed Communal Heating.
Solar thermal may work well in such applications, with storage positioned close to solar thermal arrays, charging during the day in preparation for overnight low load provision.
1st Diversity Field Trial
Below are three screen shots from two days in a row (days 8 & 9) of the total DHW loads from the 2 bed system been used to examine diversity for a retired couple.
The reason for posting it is, it demonstrates the theory nicely. You can spot the additional load from yesterday, with a new peak just after the highest peak. The peaks last approx 4 seconds each and are 10 minutes apart.
9 days of data - or 9 HIUs - gives a peak of 52kW against a potential peak of 342kW if all HIUs drew 38kW at the same time. Danish diversity gives 85kW. But this is too few HIUs to define a standard from.
If we want diversity up to say 1000 properties, then the proposition is:
Monitor 10 HIUs for 100 days gives you 1000 days of data from which you can create a standard for UK diversity, that is more relevant than the Danish standard referred to in guidance (but not yet translated into English).
Live system on http://heatweb.ddns.net:1881/diversity