DATA SPLIT Technical data

From Heatweb Wiki
Revision as of 11:46, 13 August 2018 by JL (talk | contribs) (Created page with "{| class="wikitable" |- ! DESCRIPTION !! DATA SPLIT |- ! Primary |- | Nominal primary supply temperature|| 80°C |- | Maximum primary supply temperature || 95°C * |- | Minim...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigationJump to search
DESCRIPTION DATA SPLIT
Primary
Nominal primary supply temperature 80°C
Maximum primary supply temperature 95°C *
Minimum primary supply temperature 55°C **
Maximal primary differential pressure (without dP regulator) 250kPa
Maximal primary differential pressure (with dP regulator) 450kPa
Minimal primary differential pressure 50kPa ***
Pressure class DH circuit PN16
Domestic Hot Water
Nominal DHW supply temperature 55°C
DHW Set Range 45°C to 60°C
Domestic Hot water heat exchanger (DHW) E8LAS‐40
Pressure class DHW circuit PN10
Central Heating
Return Temp Limit Range 35°C to 65°C
CH Limit Range 30°C to 80°C
Central heating heat exchanger (CH) E8LAS‐40
Pressure class CH circuit (3 bar safety valve) PN10
CH Maximum working pressure 2.5 Bar
General
Primary connections ¾” Female / 18mm
Mains & DHW connections ¾” Female / 18mm
Central heating connections ¾” Female / 18mm
Pressure relief 15mm
Casing width 490mm
Casing height 640mm
Casing depth 275mm
Casing Material EPP Expanded Polypropylene
Maximum Heat Losses 50W (1.2 kWh/day)
Typical Heat Losses (DHW Only, Keep Warm) 25W
Weight (basic version) 24kg ****
Electrical supply info 230V 50Hz
Fuse ratings 3 Amp
Sensor DHW NTC 10kohm @ 25°C
Keep Warm Modes Economy / Comfort
Max Return Temperature during Keep Warm Mode DHW Setpoint -2°C

.* Maximum primary supply temperature 100°C for momentary spikes.
.** Minimum required DH supply temperature is DHW setpoint + 5°C with a minimum of 55°C.
.*** Depends on requested DHW output and available DH supply temperature.
.**** Unit weight may vary depending on the optional components built into the unit